ESFR-17 Electronically Controlled Sprinkler
For Use in the EAS-1 Electronically Activated Sprinkler System

Enhanced Protection with Less Water
This ESFR-17 sprinkler is the first UL / C-UL Listed electronically activated sprinkler head – all system components also have the same listings. Here’s how the system works. Sprinklers are installed on existing system piping. Each sprinkler has an attached heat sensor, which are wired back to a suppression releasing panel. During a fire event, heat sensors detect a fire. The system identifies the fire location and the suppression releasing panel sends a signal to simultaneously activate only the sprinklers required to address the fire.

Benefits

Use your Existing Infrastructure
Avoid the cost of new pipe and fire pumps with a retrofit solution that replaces the sprinkler heads on your existing piping.

Maximize Warehouse Flexibility
Change storage arrangements and commodity classifications without changing your fire protection system.

Lower Fire Risk Profile
Reduced potential for direct and indirect property damage and loss of downtime due to fire.

Reduce Fire and Water Damage
Earlier detection means 60% smaller fires and significantly reduced water damage, and minimized clean-up costs.
Technical Specification
Application | Storage/Warehouse | Hazard | Storage - High |
Max # of Heads | 3,000 heads per EAS-1 control unit | Max Working Water Pressure | 175 psi (12,1 bar) |
Orientation | Pendent | Wrench | W21 |
K-Factor | 16.8 | Thread | ¾-inch |
Approvals | UL and C-UL Listed | SIN Number | TY720 |
Install Requirements | Co-located heat sensor must be installed within 12 inches (30,5 cm) laterally and 36 inches (0,9 m) vertically | Note | See Technical Data Sheet for details |
Related Products

EAS-1 Sprinkler Control Heat Sensor
- Approvals : UL and C-UL Listed
- Hazard: Storage - High

EAS-1 Control Unit
- Approvals : UL and C-UL Listed
- Hazard: Storage - High
- CPU Capacity: 3,000 addressable Sprinkler Control Heat Sensors

SprinkCAD Software Suite
Save time and ensure quality with the SprinkCAD software suite. Developed to offer fire sprinkler system designers a powerful set of digital tools to create precise solutions.
Learn about our all-in-one software package