Accelerators
Automatic, Field-Adjustable Devices
Need a device to maintain your sprinkler system pressure? We’ve got you covered. Looking for a way to reduce corrosion and extend the life of your sprinkler system? We can help with that, too.
Use the resources below to learn more about our products.
- Designed to trip when system air pressure drops at a rate exceeding approximately 1 psi/minute (0.07 bar/min)
- Maximum water supply pressure: 250 psi (17,2 bar)
- Upon tripping, it transmits system air pressure to the intermediate chamber of the dry pipe valve, which neutralizes the differential pressure holding the valve closed and opens the waterway clapper
- Easy button-press for test and reset function
- Electronically self-supervising technology, like that used in typical alarm panels for alarm and detection systems
- Battery backup in the event of primary power failure
- Operation of Tyco DPV-1 dry pipe or DV-5A preaction valve within four seconds
- Control up to two QRS-2 switches on one to two system risers (Tyco Model DPV-1 Valve with AutoPulse Z-10 or AutoPulse Z-20 Releasing Panel)
- Ideal to retrofit existing mechanical accelerators where a releasing panel is already installed
Hide
Show product comparison
  |   |   |   |