Ultra K17 Sprinkler
The Ultra K17 is a UL Listed and FM Approved sprinkler for ceiling-only protection in cold storage applications. It helps protect a wide-range of commodities with less repair and downtime risk by eliminating damage-prone in-rack sprinklers.
Designed for Ceiling-only Protection
Benefits
Quell / Vanquish provides the highest ceiling only protection in the industry for cold storage applications.
Ceiling-only coverage eliminates damage-prone in-rack sprinklers and also allows storage arrays to be changed without redesigning fire protection.
This system is based on extensive data from 15 full-scale fire tests over a range of commodity types, storage arrangements, and ceiling / storage heights.
Technical Specification
Approvals | UL Listed, FM Approved | Hazard | Storage / Class I through Cartoned Group A Plastics |
Orientation | Upright | K-Factor | 16.8 |
Temperature Rating | 155°F (68°C) & 200°F (93°C) | Response | Standard |
Thread | ¾-inch | Sin Number | TY7153 |
Note | To be installed only by a licensed Quell / VanQuish contractor in accordance with the applicable technical data sheet |
Related Products
Ultra K34 Sprinkler
- Approvals: FM Approved
- Orientation: Upright
- K-Factor: 33.6
DV-5A Pretrim Preaction Valve
- Integrated alarm port eliminates check valve in preaction systems
- UL and C-UL Listed, FM and VdS Approved
NG-1 Nitrogen Generator, Wall Mounted
- Controls oxygen corrosion in dry and preaction fire sprinkler systems
- Reduced equipment footprint with no need for a nitrogen tank or refrigerated air dryer
SprinkCAD Software Suite
Save time and ensure quality with the SprinkCAD software suite. Developed to offer fire sprinkler system designers a powerful set of digital tools to create precise solutions.
Learn about our all-in-one software package