Flat Spray Sprinklers Upright and Pendent, K-factor=57, 80, and 115 (metric)
Features:
The Model TY-FRFS, TY-FS Special, and TY-FS, Upright and Pendent, Flat Spray Sprinklers are intended for installation in accordance with CEA 4001 or EN12845, as applicable.
They produce a flatter spray pattern than standard spray sprinklers, enabling them to be used with lower clearance above the suspended open ceilings and in racks.
The Model TY-FRFS with its 3 mm diameter heat sensitive bulb element is rated quick response.
The Model TYFS Special with its 4 mm diameter heat-sensitive bulb element is rated special response.
The Model TY-FS with its 5 mm diameter heat sensitive bulb element is rated standard response "A".
Hazard: Special Temperature: 57, 68, 79, 93, 141 (C) Thread: 3/8" Approval: LPCB, VdS Response: Quick Response SIN Numbers: TY1136 Wrench: W6 Tech Data Sheet:View TFP635 Tech Data Translations[PDF]:CS, DE, ES, FR, HU, IT, NL, PL, RU
WARNING: Cancer and Reproductive Harm -- www.P65Warnings.ca.gov
Tech Data Sheet - TFP2300 - Regulatory and Health Warnings
The purpose of Proposition 65 is to ensure the public is informed about the potential exposure to chemicals known to cause cancer,
birth defects, or other reproductive harm.
The law requires the State of California to publish a list of these chemicals.
This list currently contains ~1,000 chemicals; chemicals are added and removed regularly.
Johnson Controls products may have traces of various chemicals that are on the list,
however they are all a part of the normal manufacturing, distribution or labeling process.