TFPlogo
 
Tyco Fire Products Brand

Horizontal Sidewall
Standard and Quick Response, Extended Coverage, K-factor=5.6


Features:
  • EC light hazard
  • Lengths up to 48" (1220 mm)
  • Designed for use in light hazard occupancy applications requiring a dry sprinkler to cover areas up to: 16Ft. x 20Ft. (4,9 m x 6,1 m) or 18Ft. x 16Ft. (5,5 m x 4,9 m)
  • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates
Hazard: Light Hazard
Temperature: 135, 155
Thread: 1"
Approval: UL, C-UL, NYC
Response: Standard Response,Quick Response
SIN Numbers: TY3358,TY3338
Wrench: Pipe Wrench
Wrench [Recessed]: W17
Tech Data Sheet: TFP520 View |  PDF 308kb
Tech Data Translations[PDF]: SV